GFCI Instructions
FOR INSTALLATION OF A (2) TWO-POLE GFCI-CIRCUIT BREAKER INTO A LOAD CENTER. THESE ASSEMBLIES ARE
DESIGNED ESPECIALLY FOR USE BY QUALIFIED ELECTRICIANS TO MEET THE SWIMMING POOL & SPA REQUIRE-
MENTS OF ARTICLES 680-12 & 680-42 OF THE 1996 NATIONAL ELECTRICAL CODE (NEC) 680-12. DISCONNECTING
MEANS SHALL BE ACCESSIBLE, LOCATED WITHIN SIGHT OF POOL, SPA EQUIPMENT, AND SHALL BE LOCATED AT
LEAST (5) FIVE FEET HORIZONTALLY FROM INSIDE WALLS OF THE POOL, SPA OR HOT TUB. NATIONAL ELECTRIC
CODE (NEC) 682-42. PROTECTION OF AN OUTLET THAT SUPPLIES A SELF CONTAINED SPA OR HOT TUB EQUIPMENT
ASSEMBLY, ALL SPA EQUIPMENT SHALL BE PROTECTED BY A (GFCI) GROUND-FAULT CIRCUIT INTERRUPTER. TO
ENSURE THAT PEOPLE IN THE SPA ARE PROTECTED.
INSTALLATION OF THE GFCI CIRCUIT BREAKER, INCLUDING AMP SIZING AND SELECTION OF CONDUCTOR SIZE &
TYPE, MUST BE INSTALLED BY A QUALIFIED ELECTRICIAN, IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE
(NEC), OWNERS MANUAL, AND ALL FEDERAL, STATE AND LOCAL CODES AND REGULATIONS IN EFFECT AT THE
TIME OF INSTALLATION. A LOAD NEUTRAL CONNECTION IS REQUIRED, BECAUSE SPAS CONTAIN BOTH 115 AND 240
VOLT EQUIPMENT. THE GFCI LINE NEUTRAL WIRE (PIGTAIL) MUST BE CONNECTED IN ALL INSTALLATIONS. THE
GFCI WILL NOT OPERATE CORRECTLY WITHOUT CONNECTION OF LINE NEUTRAL WIRE TO AN INCOMING LINE NEU-
TRAL.
HOUSE BREAKER BOX
SPA LOAD BOX
WIRING DIAGRAM (240
VAC)
FOR LICENSED ELECTRICIAN ONLY
NOTE: USE COPPER CONDUCTORS ONLY
Input From Power
Pole Transformer
Neutral
(Ground Bar)
WARNING:
THIS
WIRING MUST BE DONE BY A LICENSED ELECTRICIAN.
HOT
HOT
IF
THE SPA IS
WIRED INCORRECTLY;
YOUR
WARRANTY IS
VOID!!!
A
B
BREAKER
BREAKER
GRN (Ground)
Black (Hot)
30/50 Amp, 60 Hz GFCI Breaker (2 Hots, 1 Neutral, 1 Ground)
Ground Bar
Terminal Block
4
BREAKER
BREAKER
Red (Hot)
White (Neutral)
GRN (Ground)
Red (Hot)
Red
3
Wht
2
Red
Red
White
Black
To spa circuit
board (see
configuration
Blk
1
Black (Hot)
Black
options below)
Spa Cabinet
Electrical Box
Insulated Power Cord (2 Hots, 1 Neutral, 1 Ground)
GFCI SUB PANEL
Wht (Neutral)
Red
(Hot)
.
Blk
(Hot)
GRN (Ground)
Ground Bar
White (Neutal) From
Load Neutral
Red
(Hot)
Blk
(Hot)
GRN (Ground)
CAUTION!
Use #6 AWG
Copper Wire
Only.
Insulated Power Cord
(2 Hots, 1 Neutral, 1 Ground)
White (Neutral) From Line
Neutral (GFCI Pigtail)
CIRCUIT BOARD CONFIGURATION OPTIONS
All Model 62, Model 65, and Monarch spas are factory configured for a
JP2 JP2
240 VAC 50 amp service. In this configuration, the heater will operate
while both jet pumps are running. An alternate 30 amp service can be
configured for locations where 50 amp service is unavailable. In this
configuration, the heater will not operate while both jet pumps are
1 2 3 4 5 6 7 8
Factory
50 Amp @
1 2 3 4 5 6 7 8
Alternate
30 Amp @
Place
Jumper
running. To configure spa for 30 amp service, place a jumper across
the circuit board's JP2 jumper position #8 as shown (right).
240 VAC Service
Configuration
Here!
240 VAC Service
Configuration