ELECTRICAL INSTALLATION REQUIREMENTS 
For All Models Except TS 120 
HAVE YOUR ELECTRICIAN READ THE FOLLOWING INFORMATION BEFORE 
INSTALLATION BEGINS
Electrical connections made improperly, or the use of wire gauge sizes for incurring 
power which are too small, may continually blow fuses in the electrical equipment box, 
may damage the internal electrical controls and components, may be unsafe and in any 
case will void your warranty.
It is the responsibility of the spa owner to ensure that electrical connections are made by 
a qualified electrician in accordance with the National Electrical Code and any local and 
state electrical codes in force at the time of installation.
These connections must be made in accordance with the wiring diagrams found inside 
the control box. This equipment has been designed to operate on 60Hz. alternating 
current only, 240 volts are required. Make sure that power is not applied while perform-
ing any electrical installation. A copper bonding lug has been provided on the electrical 
equipment pack to allow connection to local ground points. The ground wire must be 
at least 8 AWG copper wire (unless local or state codes require a heavier gauge wire) 
and must be connected securely to a grounded metal structure such as a cold water 
pipe. All Master Spas equipment packs are wired for 240 VAC only. The only electrical 
supply for your spa must include a 50 AMP switch or circuit breaker to open all non-
grounded supply conductors to comply with section 422-20 of the National Electrical 
Code. The disconnect must be readily accessible to the spa occupants, but installed at 
least five feet from the spa. A Ground-Fault Circuit Interrupter (GFCI) must be used to 
comply with section 680-42 of the National Electrical Code. A ground fault is a current 
leak from any one of the supply conductors to ground. A GFCI is designed to automati-
cally shut off power to a piece of equipment when a ground fault is detected.
Power hook-up to the spa must be 240 volt 3 wire plus ground (6 AWG copper) 8 AWG 
copper ground wire.
Route the cable into the equipment area for final hook-up to terminals inside the con-
trol panel. The spa must be hooked up to a “dedicated” 240 volt, 50 amp breaker and 
GFCI. The term “dedicated” means the electrical circuit for the spa is not being used for 
any other electrical items (patio lights, appliances, garage circuits, etc.). If the spa is con-
nected to a non-dedicated circuit, overloading will result in “nuisance tripping” which 
requires resetting of the breaker switch at the house electrical panel. 