Troubleshooting guide
7
Branch
AWG (mm
2
) Wire Gauge Size at 90° C
Voltage/ Full Circuit Dist in Ft. (M) - Service to Motor
Model Hertz Load Breaker 0-100 101-200 201-300
No. (1 Phase) Amps Amp Rating (0-30) (31-60) (61-90)
Two-Speed Pumps:
DJAYGB-9013, -9113 230 /60 8.5 / 3 15 14 (2) 14 (2) 12 (3)
DJAYGB-9051M, -9151M 230 /60 8.5 / 3 15 14 (2) 14 (2) 12 (3)
DJAYGB-9051MB, -9151MB 230 /60 8.5 / 3 15 14 (2) 14 (2) 12 (3)
DJAYHB-0001 230 /60 12 / 3.7 15 14 (2) 14 (2) 12 (3)
DJAYHB-0041, -0141 230 /60 12 / 3.7 15 14 (2) 14 (2) 12 (3)
DJAYHB-0051M, -0151M 230 /60 12 / 3.7 15 14 (2) 14 (2) 12 (3)
DJAYHB-0055M, -0155M 230 /60 12 / 4.4 15 14 (2) 14 (2) 12 (3)
DJAYHB-0061, -0161 230 /60 12 / 3.7 15 14 (2) 14 (2) 12 (3)
DJAYHB-0071M 230 /60 12 / 3.7 15 14 (2) 14 (2) 12 (3)
DJAYHB-0097 230 /60 12 / 3.7 15 14 (2) 14 (2) 12 (3)
DJAYHB-3021, -3121 230 /60 12 / 3.7 15 14 (2) 14 (2) 12 (3)
DJAYHB-3021H, -3121H 230 /60 12 / 3.7 15 14 (2) 14 (2) 12 (3)
DJAYHB-9041, -9141 230 /60 12 / 3.7 15 14 (2) 14 (2) 12 (3)
TABLE IA (Continued)– RECOMMENDED CIRCUIT BREAKER SIZE AND WIRING DATA
NOTE: The second character of the model number suffix (the four characters following the dash) on pumps packed in bulk will be a “1”
(for example, – 3115). Identical pumps packed individually will have a suffix with a “0” replacing the “1” (for example – 3015).
When replacing a pump having a suffix “-X1XX”, order the same model with suffix “-X0XX”. When replacing a pump having a suffix “-X0XX”,
do not change the suffix.