Specifications
3
Typical GFCI Load Center
(Not Supplied With Spa)
POWER REQUIRMENTS
AMP
MODEL VOLTS AMPS LOAD MARKING APPLICATION
Platinum 2020 240 60 48 3 wire#6 + Grd 3 HS2000VS
WARNING - ALWAYS USE A CERTIFIED ELECTRICIAN WHEN HOOKING UP YOUR NEW SPA.
G.F.C.I Breaker
Figure 1
Load 120 Volts
(Black) To Spa
Ground (Green)
Input
Load Neutral Bar
From House To Box
(Black) Input
From House To Box
Neutral (White) Input
From House
To Box (Red)
Input
Load Neutral
(White) To Spa
Load 120 Volts
(Red) To Spa
BREAKER BOX
(Minimum) 6 Gauge
Copper Wire Must
Be Used
Pig Tail (White) From
GFCI Breaker Going
To Neutral Bar In Box
Ground Bar Attached
To Box (Green) Input
& Out
NOTE: The White Neutral Wire from the GFCI
MUST be connected to an incoming Line Neutral.
The internal mechanism of the GFCI requires
this Neutral connection. The GFCI WILL NOT
WORK WITHOUT IT.