Operating instructions

Issue 10/06 3 Functions
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
93
Table 3-11 Parameter P0731 (frequently used functions / states)
Parameter value Significance
52.0 Drive ready
52.1 Drive ready to run
52.2 Drive running
52.3 Drive fault active
52.4 OFF2 active
52.5 OFF3 active
52.6 Switch-on inhibit active
52.7 Drive warning active
52.8 Deviation, setpoint / actual value
52.9 PZD control (Process Data Control)
52.A Maximum frequency reached
52.B Warning: Motor current limit
52.C Motor holding brake (MHB) active
52.D Motor overload
52.E Motor running direction right
52.F Inverter overload
53.0 DC brake active
53.1 Act. frequency f_act >= P2167 (f_off)
53.2 Act. frequency f_act > P1080 (f_min)
53.3 Act. current r0027 >= P2170
53.6 Act. frequency f_act >= setpoint
NOTE
A complete list of all of the binary status parameters (refer to "CO/BO" parameters)
can be taken from the parameter list.