Operating instructions

Issue 10/06 3 Functions
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
85
P2267 =...
Max. value for PID feedback
Sets the u
pp
er limit for the value of the feedback si
g
nal in
[
%
]
..
P2268 =...
Min. value for PID feedback
Sets lower limit for value of feedback si
g
nal in
[
%
]
..
P2280 =...
PID proportional gain
Allows user to set
p
ro
p
ortional
g
ain for PID controller.
P2285 =...
PID integral time
Sets inte
g
ral time constant for PID controller.
P2291 =...
PID output upper limit
Sets u
pp
er limit for PID controller out
p
ut in
[
%
]
.
P2292 =...
PID output lower limit
Sets lower limit for the PID controller out
p
ut in
[
%
]
.
PID
MOP
ADC
PID
SUM
PID
PID
FF
USS
BOP link
USS
COM link
CB
COM link
P2254
P2253
PID
RFG
PID
PT1
PID
P2200
P2264
PID
PT1
PID
SCL
Output
PID
0
1
Motor
control
P2257
P2258
P2261
P2271
P2269
P2270
P2265
P2280
P2285
P2268
P2267
P2292
P2291
r2273
r2294
Example:
Parameter Parameter text Example
P2200 BI: Enable PID controller P2200 = 1.0 PID controller active
P2253 CI: PID setpoint P2253 = 2224 PID-FF1
P2264 CI: PID feedback P2264 = 755 ADC
P2267 Max. PID feedback P2267 Adapt to the application
P2268 Min. PID feedback P2268 Adapt to the application
P2280 PID proportional gain P2280 Determined by optimizing
P2285 PID integral time P2285 Determined by optimizing
P2291 PID output upper limit P2291 Adapt to the application
P2292 PID output lower limit P2292 Adapt to the application
NOTE
If P0971 is used to start data save from the RAM to EEPROM, then after the data
has been transferred, the communications memory is re-initialized. This means that
communications via USS as well as also via the CB board are interrupted for the
time it takes to reset:
The connected PLC (e.g. SIMATIC S7) goes into stop
The STARTER start-up program buffers the communications failure
For the DriveMonitor start-up program, "NC" (not connected) or "drive busy" is
displayed.
The "busy" text is displayed at the BOP operator panel
After reset has been completed, for the start-up programs STARTER and
DriveMonitor and the BOP operator panel, communications are automatically re-
established.
100.00 %
0.00 %
3.000
0.000 s
100.00 %
0.00 %