Operating instructions
3 Functions Issue 10/06
MICROMASTER 420 Operating Instructions
84 6SE6400-5AA00-0BP0
DC braking
P1232 =...
DC braking current (entered in %)
Defines level of DC current in [%] relative to rated motor current (P0305).
P1233 =...
Duration of DC braking (entered in s)
Defines duration for which DC injection braking is to be active following an OFF1 or OFF3
command.
Compound braking
P1236 =...
Compound braking current (entered in %)
Defines DC level superimposed on AC waveform after exceeding DC-link voltage threshold
of compound braking. The value is entered in [%] relative to rated motor current (P0305).
(see also "Vdc controller").
Compound braking switch-on level
P0210213.1V21.13 U mains
DC_Comp
⋅⋅=⋅⋅=
If P1254 = 0 :
1242r0.98 U
DC_Comp
⋅=
Compound braking switch-on level
otherwise :
Vdc controller
P1240 =...
Configuration of Vdc controller
Enables / disables Vdc controller.
0 Vdc controller disabled
1 Vdc-max controller enabled
P1254 =...
Auto detect Vdc switch-on levels
Enables/disables auto-detection of switch-on
levels for Vdc control functionalities.
0 Disabled
1 Enabled
t
t
⏐f⏐
1
-controller active
V
DC_max
t
V
DC
0
r0056 Bit14
r1242
A0911
f
f
act
set
PID controller
P2200 =...
BI: Enable PID controlle
r
PID mode Allows user to enable/disable the PID controller. Setting to 1 enables the PID
controller. Setting 1 automatically disables normal ramp times set in P1120 and P1121 and
the normal fre
q
uenc
y
set
p
oints.
P2253 =...
CI: PID setpoint
Defines set
p
oint source for PID set
p
oint in
p
ut.
P2254 =...
CI: PID trim source
Selects trim source for PID setpoint. This signal is multiplied by the trim gain and added to
the PID set
p
oint.
P2257 =...
Ramp-up time for PID setpoint
Sets the ram
p
-u
p
time for the PID set
p
oint.
P2258 =...
Ramp-down time for PID setpoint
Sets ram
p
-down time for PID set
p
oint.
P2264 =...
CI: PID feedback
Selects the source of the PID feedback signal.
100 %
0 s
0 %
1
1
0.0
0.0
0.0
1.00 s
1.00 s
755.0