Operating instructions

Issue 10/06 2 Installation
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
29
2.4.2 Power and motor connections
WARNING
The inverter must always be grounded.
Isolate the mains electrical supply before making or changing connections to
the unit.
Ensure that the motor is configured for the correct supply voltage: single /
three-phase 230 V MICROMASTERS must not be connected to a 400 V
three-phase supply.
When synchronous motors are connected or when coupling several motors in
parallel, the inverter must be operated with voltage/frequency control
characteristic (P1300 = 0, 2 or 3).
CAUTION
After connecting the power and motor cables to the proper terminals, make sure
that the covers have been replaced properly before supplying power to the unit!
NOTICE
Ensure that the appropriate circuit-breakers/fuses with the specified current
rating are connected between the power supply and inverter (see chapter 5,
Tables starting on page 186).
Use Class 1 60/75
o
C copper wire only (for UL compliance). For tightening
torque see Table 5-2, page 185.
Operation with long cables
All inverters will operate at full specification with cable lengths up to 50 m screened
or 100 m unscreened.
When using output reactors as shown in Catalog DA 51.2, the following cable
lengths are possible:
Supply Voltage 200 V … 240 V ± 10 % 380 V … 400 V ± 10 % 401 V … 480 V ± 10 %
Frame Sizes A … C A … B C A … C
Shielded 200 m 150 m 200 m 100 m
Non-shielded 300 m 225 m 300 m 150 m
CAUTION
When using output reactors and LC filters, operation up to a pulse frequency of 4
kHz only is permitted. Please ensure that the automatic pulse frequency reductions
are also deactivated. Mandatory parameter settings when using an output reactor:
P1800 = 4 kHz , P0290 = 0 or 1.