Operating instructions
Issue 10/06 6 Options
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
191
6 Options
An overview of the options available for the MICROMASTER 420 is given in this
section. For further information about options, please refer to the catalog or the
documentation CD.
6.1 Device-independent options
Basic Operator Panel (BOP)
Advanced Operator Panel (AOP)
PROFIBUS module
PC to inverter connection kit
PC to AOP connection kit
BOP/AOP door mounting kit for single inverter control
AOP door mounting kit for multiple inverter control
"DriveMonitor” and "Starter" commissioning tool
6.2 Device-dependent options
EMC filter, Class A
EMC filter, Class B
Additional EMC filter, Class B
Low leakage Class B filter
Line commutating choke
Output choke
LC filter
Gland plate
CAUTION
If using output chokes or LC filters operation is only permissible with a pulse
frequency of
4 kHz. Make shure that the automatic pulse frequency reductions are
disabled.
Coercing required parameter adjusting: P1800 = 4 kHz , P0290 = 0 or 1.