Instruction manual

Page 82 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmm
m
Open Channel Monitoring
MR 200
Cut Throat Flume
Application Information
Similar to Parshall flume except that the floor is flat bottomed and throat has no
virtual length.
Refer to manufacturer’s specifications for flow equation and point of head
measurement.
Flume Size
(pipe diameter in inches)
Point of Measurement
cm inches
4-12 2.5 1
15 3.2
18 4.4 1¾
21 5.1 2
24 6.4
30 7. 6 3
42 8.9
48 10.2 4
54 11.4
60 12.7 5
66 14.0
72 15.2 6
Parameter Index Value
P600 G 1–Cut Throat Flume
P601 G 1.55
P603 G Maximum Head (preset P007)
P604 G Maximum Flow
P606 G Time Units
Plan View