Instruction manual
Page 54 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Alarms
Alarms
Level
The level alarm is the most common. Use this alarm to warn you when your process is in
danger of being upset due to high or low levels.
Generally, the four alarms used are Hi, Hi Hi, Lo, and Lo Lo.
Set the Common Parameters
Prerequisite: You must know the details of your application and substitute the values for
the sample values provided. If you are bench testing the unit, then set your test values to
be the same as the sample values.
Parameter
Index
1
1.
This example assumes a base, single measurement unit. If your unit has
optional dual point software installed then some parameters are indexed by
two.
Value Description
P001 G 1 Operation = level
P002 G 1 Material = liquid
P003 G 2 Maximum Process Speed = medium
P004 G 102 Transducer = XPS-10
P005 G 1 Units = meters
P006 G 1.8 Empty = 1.8m
P007 G 1.4 Span = 1.4m
P007
P006
lo lo
lo
hi
hi hi