Instruction manual
Page 46 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Relays
Preset Applications
Preset applications set up the relay parameters to predetermined values shown below:
Value # Parameters Affected
Off 0 All relays set to OFF
Wet Well 1
1
Pump down with the following settings:
Parameter
Relay #
123456
P111 52 52 1(H) 1(L) 0 0
P112 70% 80% 90% 10% – –
P113 20% 20% 85% 15% – –
Wet Well 2
2
Pump down with the following level and rate settings:
Parameter
Relay #
123456
P111 52 52 1(H) 1(L) 0 0
P112 70% 80% 90% 10% – –
P113 20% 20% 85% 15% – –
P121 1
P121 sets the pump relays to accept control by rate of level change once
the first ON setpoint is reached. Because the pumps are started by rate,
you must change P703 to desired empty rate.
Reservoir 1
3
Pump up with the following level settings:
Parameter
Relay #
123456
P111 52 52 1(H) 1(L) 0 0
P112 30% 20% 90% 10% – –
P113 80% 80% 85% 15% – –
Reservoir 2
4
Pump up with the following level and rate settings:
Parameter
Relay #
123456
P111 52 52 1(H) 1(L) 0 0
P112 20% 20% 90% 10% – –
P113 80% 80% 85% 15% – –
P121 1
P121 sets the pump relays to accept control by rate of level change once
the first ON setpoint is reached. Because the pumps are started by rate
you must change P702 to desired fill rate.
Screen
5
Differential control of a screen or rake:
Parameter
Relay #
123456
P110 312300
P111 50 1(H) 1(L) 1(H) – –
P112 80% 90% 10% 90% – –
P113 20% 85% 15% 10% – –
Alarms
6
General alarms at four setpoints:
Parameter
Relay #
123456
P111 1(H) 1(L) 1(HH) 1(LL) 0 0
P112 80% 20% 90% 10% – –
P113 75% 25% 85% 15% – –