Page 38 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Operation
Example [MR 200 only]
P054 provides up to 32 breakpoint levels used with P055 (Volume Breakpoint) for universal
volume calculation. The illustration indicates how you can set secondary indexes to
specific functions.
P054 [1,1]
=
.75m
sets breakpoint 1 on transducer 1 to .75m.
P054 [2,1] = 8m
sets breakpoint 1 on transducer 2 to 2.75m.
Starting Measurement
The MultiRanger startup varies between single and dual point models.
Single Point Models
The MultiRanger starts in DISTANCE mode with the transducer preset for the XPS-10 and
an empty distance of 5 meters. Change the following parameters to reflect your
application parameters.
A B C
P054 [1,6] = 2m P054 [1,3] = 1.5m P054 [1,1] = .75m
P054 [2,6] = 8m P054 [2,3] = 5.5m P054 [2,1] = 2.75m
Parameter Index Value Description
P001 G 1 Operation = level
P002 G 1 Material = liquid
P003 G 2 Maximum Process Speed = medium
P004 G 104 Transducer = XPS-15
P005 G 1 Units = meters
P006 G 12 Empty = 12m
P007 G 10 Span = 10m
A
C
B
1
2
P054
[6 = 2m]
[3 = 1.5m]
[1 = 0.75m]
[1 = 2.75m]
[3 = 5.5m]
[6 = 8m]
A
B
C