Page 26 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Operation
Setting the Default Auxiliary Reading
To maintain a constant variable display in the auxiliary reading area, set the default.
Example:
To leave the level reading on the screen and view the echo confidence in the auxiliary
reading field, set the following parameter:
Setting a Specific Auxiliary Reading
To display a second auxiliary reading, press in RUN mode.
Example: To set to display current temperature, go to P731:
Multiple Readings [MR 200 only]
During differential or average operation (P001 = 4 /5), the display scrolls sequentially
through Point Numbers 1, 2, and 3. Point 3 is the difference between (or average of) Points
1 and 2.
Changing Number Scrolling Speed
See
Parameter Indexing
on page 37. All the instructions in the following procedures apply
to the hand programmer and assume that the MultiRanger is activated.
Parameter Index Value Description
P730 G 805 Auxiliary field defaults to P805
Parameter Index Value Description
P731 G 912 Shows P912–Transducer Temperature
Parameter Index Value Description
P732 G 5 Hold each value for 5 seconds
P