Page 204 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Parameters
P820 Algorithm
Chooses the algorithm to generate the measured value from the profile.
Use this to select the algorithm(s) the Sonic Intelligence® echo selection is based on.
Use P805 Echo Confidence (page 202) to determine which algorithm gives the highest
confidence under all level conditions. If the wrong echo is processed, observe the echo
processing displays and select an alternate algorithm, either by entering the numeric
value desired, or as below:
1. Press MEASURE to display the Auxiliary Function symbol.
2. Press ARROWS to access the desired Reading display symbols.
3. Press ENTER when the required algorithm is displayed.
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values 1 ALF = flat Area, Largest, and First average
2 A = flat Area only
3 L = flat Largest only
4F = flat First only
5 AL = flat Area and Largest average
6 AF = flat Area and First average
7 LF = flat Largest and First average
8 * bLF = smooth Largest or First
9 bL = smooth Largest only
10 bF = smooth First only
12 tF = true First only
Related
• P805 Echo Confidence
• P821 Spike Filter
• P822 Narrow Echo Filter
• P823 Reform Echo
• P825 Echo Marker Trigger