7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 201
mmmmm
Parameters
P803 Shot / Pulse Mode
Determines what type of ultrasonic shots are fired.
Increases MultiRanger response when the monitored surface is close to the transducer
face. Select short and long to have short and long acoustic shots fired for each
measurement, regardless of the transducer to surface distance. Select short to have only
short shots fired if the Echo Confidence (P805) produced by a short shot exceeds the
short Confidence Threshold (P804) and the monitored surface is always within the Short
Shot Range (P852).
P804 Confidence Threshold
Determines which echoes are evaluated by software.
The short and long shot Confidence Thresholds are preset to 10 and 5 respectively. When
Echo Confidence (P805) exceeds the Confidence Threshold, the echo is evaluated by
Sonic Intelligence®. Values are entered as two numbers separated by a decimal point.
The first number is the short shot confidence and the second number is the long shot
confidence.
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values
1Short
2 * Short and long
Related
P006 Empty
P805 Echo Confidence
P804 Confidence Threshold
P852 Short Shot Range
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values
Range: 0 to 99:0 to 99
Preset: 10:5
Related P805 Echo Confidence
Note: The decimal point is replaced with a colon (:) on the display.