7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 187
mmmmm
Parameters
P708 Volume Rate Display [MR 200]
The rate of change of volume in percent of maximum volume per minute.
Please note that this feature applies to the MultiRanger 200 only.
This value is used internally to calculate inflow in pumped volume applications (P622=3).
Press READING to toggle between percent and volume.
Measurement Verification (P710 to P713)
P710 Fuzz Filter
Use this to stabilize the reported level, due to level fluctuations (such as a rippling or
splashing liquid surface) within the Echo Lock Window (P713).
This value (in % of Span, P007) is automatically altered when Maximum Process Speed
(P003) is altered. The higher the value entered, the greater the fluctuation stabilized.
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values Range: -999 to 9999 (view only)
Related • P622 Inflow / Discharge Adjust
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values Range: 0 to 100 (0 = off)
Altered by • P003 Maximum Process Speed
Related
• P007 Span
• P713 Echo Lock Window