Page 176 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Parameters
P633 LCD Totalized Decimal Position [MR 200]
Enter the maximum number of decimal places to be displayed.
In RUN mode, the number of decimal places displayed is not automatically adjusted.
When the LCD Total value is so large as to exceed display capabilities, the total rolls over
to 0 and continues incrementing.
P640 Remote Totalized Multiplier [MR 200]
Use this feature if the remote totalizer (device connected to the relay set for totalizer
operation [relay Function, P111 = 40]), updates too slowly or rapidly.
Parameter is relevant only if Operation is set to OCM or Pumped Volume (P001 = 6 or 7).
The relays on the MultiRanger have a maximum frequency of 2.5 Hz.
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values
0 no digits after the decimal point
1 1 digit after the decimal point
2 * 2 digits after the decimal point
3 3 digits after the decimal point
Related • LCD Totalizer (P322 and P323)
Note: Set the decimal position during initial commissioning of the MultiRanger
200. If the position is changed later, the totalizer data in P322 and P323 will be
incorrect and must be reset according to the new decimal value.
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values
-3 .001
-2 .01
-1 .1
0*1
Values
110
2100
3 1000
4 10,000
5 100,000
6 1,000,000
7 10,000,000
Related
•P001 Operation
• P111 Relay Control Function
• P114 Relay Duration Setpoint
• P115 Relay Interval Setpoint
• P645 Relay Duration