Instruction manual

7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 163
mmmmm
Parameters
P336 Auto Record Filling / Emptying
Use this feature to restrict Auto Profile Records from being saved unless the level is
rising, falling or either.
If the level changes at a rate in excess of the corresponding Filling / Emptying Indicator
(P702 / P703) values, the Echo Profile is saved subject to this and other Auto Profile
Record restrictions.
P337 Auto Record LOE Time
Limits Auto Profile Records from being saved unless extended LOE occurs.
If the LOE condition exceeds the period entered, the Echo Profile is saved. When set for 0
LOE is not required for an Auto Profile Record to be saved.
Primary Index Global
Values
0 * Auto Profile Record on filling or emptying
1 Auto Profile Record on filling only
2 Auto Profile Record on emptying only
Related
P334 Auto Record ON Setpoint
P335 Auto Record OFF Setpoint
P337 Auto Record LOE Time
P702 Filling Indicator
P703 Emptying Indicator
Primary Index Global
Values
Range: 0.0 to 9999 (seconds)
Preset: 0.0
Related
P334 Auto Record ON Setpoint
P335 Auto Record OFF Setpoint
P336 Auto Record Filling / Emptying