7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 157
mmmmm
Parameters
P309 Pump RUN Time
Displays the amount of time in minutes since a relay was last activated.
Parameter measures the length of time since a relay was asserted, most often to
determine how long a pump has been running. Alternatively, it can monitor a relay to
show how long it has been in a state of alarm. It resets every time the relay is activated.
P310 Pump Hours
View or reset the accumulate ON time for the displayed Relay Number.
Value is displayed with a floating decimal point (the more figures displayed before the
decimal, the fewer displayed after). It is the value displayed when key is pressed in
the RUN mode.
P311 Pump Starts
View or reset the accumulated number of times the Relay Number has been ON.
This value is displayed when key is pressed and held for five seconds in RUN mode.
P312 Pump Run Ons [MR 200]
View or reset the accumulated number of times the displayed Relay Number has been
held ON via Run On Interval (P130).
Please note that this parameter applies to the MultiRanger 200 only.
Primary Index Relay
Values Range: 0 to 9999 minutes (view only)
Related • Relay Function (P111) set for any pump control feature
Primary Index Relay
Values Range: 0.000 to 9999
Related • Relay Function (P111) set for any pump control feature
Primary Index Relay
Values Range: 0 to 9999
Related • Relay Function (P111) set for any pump control feature
Primary Index Relay
Values Range: 0 to 9999
Related • Relay Function (P111) set for any pump control feature