Page 154 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Parameters
P270 Discrete Input Function
Sets how discrete signals are interpreted by the MultiRanger.
P275 Scaled Discrete Input Value
Shows the current value of the discrete input after any scaling is applied.
Readings are updated continuously even in PROGRAM mode. The value signals a level
override event.
Standard Data Logging (P300 to P321)
All records can be reset by pressing the CLEAR keys.
Record Temperatures (P300 to P303)
These features display the high and/or low temperatures in °C. When a parameter
relating to a TS-3 Temperature Sensor is accessed, the Point Type display changes to the
TS-3 symbol .
If the unit is powered up without a temperature sensor connected, the value –50°C is
displayed. This information can help trace problems with both built in and external
temperature sensors.
Primary Index Discrete input
Values
0Forced OFF
1Forced ON
2 * Normally Open – 0 (DI open), 1 (DI closed)
3 Normally Closed – 0 (DI closed), 1 (DI open)
Related • Pump Control section
Primary Index Discrete input
Values
Display: view only
Values: dependent on the function of the discrete input
Range of Values Function (P270)
1Forced ON
0Forced OFF
0 (DI open), 1 (DI closed) Normally Open
0 (DI closed), 1 (DI open) Normally Closed