Instruction manual
Page 152 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Parameters
P250 mA Input Range [MR 200]
Shows the mA input range of the connected mA device.
Ensure this range corresponds to the output range of the external device. All level
measurements will equate % of Span with the % of the mA range.
P251 0 or 4 mA Input Level [MR 200]
Shows the process level corresponding to the 0 or 4 mA value.
When using an external mA signal to determine level, the input range must be scaled to
give accurate results.
P252 20 mA Input Level [MR 200]
Shows the process level corresponding to the 20 mA value.
Input range is scaled for accuracy if an external mA signal calculates level.
Primary Index Global
Values
1 0 to 20 mA
2*4 to 20 mA
Primary Index Global
Values
Range: -999 to 9999%
Preset: 0%
Related
• P006 Empty
• P007 Span
Primary Index Global
Values
Range: -999 to 9999%
Preset: 100%
Related
• P006 Empty
• P007 Span