7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 135
mmmmm
Parameters
MultiRanger 100
MultiRanger 200
Values For P111
Control Type
#
1
1.
When reading and setting this parameter through Modbus or SmartLinx
communications the parameter values are mapped to different numbers.
See
MultiRanger Communications
on page 89 for Modbus information or
the relevant SmartLinx
®
manual.
Relay Control
General
OFF 0* Relay set off, no action (preset)
Level 1 Based on level setpoints ON and OFF
Loss of Echo (LOE) 6 When echo is lost
Cable Fault 7 When the circuit to a transducer is opened
Pump Fixed Duty Assist 50
At fixed ON and OFF setpoints and allows multiple
pumps to run
Alternate Duty
Assist
52
At rotating ON and OFF setpoints and allows multiple
pumps to run
Communication 65
Based on input from external communications. See
Communications
section on page 89 for further refer-
ence.
Values For P111
Control Type
#
1
Relay Control
General
Off 0* Relay set off, no action (preset)
Level 1 Based on level setpoints ON and OFF
In Bounds 2
When level enters the range between ON and OFF
setpoints
Out of Bounds 3
When level exits the range between ON and OFF set-
points
Rate of Change 4 Based on rate setpoints ON and OFF
Temperature 5 Based on temperature setpoints ON and OFF
Loss of Echo (LOE) 6 When echo is lost
Cable Fault 7 When the circuit to a transducer is opened
Flow
Totalizer 40 Every 10
y
units
(P641-P645)
Flow Sampler 41
Every y x 10
2
units (P641-P645) or time duration (P115)