Page 128 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Parameters
In RUN mode, the decimal position adjusts to prevent the number of digits from exceeding
the display capabilities. To keep the decimal place from shifting, reduce the number of
decimal places to that shown at 100%.
Example:
If 100% is 15m, use two decimal places for sample readings of 15.00 or 12.15.
P061 Convert Reading [MR 200]
Multiplies the current value by the specified amount to allow for scaling.
Examples:
• If the measured value is in feet, enter 0.3333 to display the number of yards
• For simple linear, volume conversions set POO5 to 1 (meters) and then enter the
volume measurement per unit to get the correct conversion. For example, if the
reservoir contains 100 litres per vertical meter, use 100 to get the reading in litres.
P062 Offset Reading
Adds the specified value to the level reading, usually to reference the reading to sea level
or another datum level.
The operation of the device is not affected by the Offset Reading. This value is used for
display purposes only. All control measurements are still referenced to Empty.
Alters • P607 Flowrate Decimal
Altered by • P051 Maximum volume
Related • P920 Reading Measurement
Primary Index Level
Values
Range: -999 to 9999
Preset: 1.000
Related • P920 Reading Measurement
Notes:
• This method does not calculate volume. It must not be used in place of the
volume parameters if any volume dependent features (such as pump
efficiency) are used. To calculate true volumes see
Volume
(P050 to P055).
• Avoid entering a value that, when multiplied by the maximum current
Reading, exceeds the display capabilities. If value exceeds four digits, EEEE is
shown.
Primary Index Level
Values
Range: -999 to 9999
Preset: 0.000
Related • P920 Reading Measurement