Instruction manual

7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 127
mmmmm
Parameters
P055 Volume Breakpoints and Characterization
(Universal Volume Calculation) [MR 200]
Each segment defined by the level breakpoints (P055) requires a volume so that the
MultiRanger can make the level-to-volume calculations.
Typical volume calculations
Entering a Volume Breakpoint
1. Go to Parameter P055.
2. For each index enter a volume.
3. Ensure that each volume corresponds to the same index for P054.
For more on
Volume Characterization
, go to page 52.
Display and Reading (P060 to P062)
These parameters are used to:
Change the number of decimal places displayed
Convert the Reading to alternate units
Reference measurements to other than Empty (P006) or Span (P007)
P060 Decimal Position
Defines the maximum number of decimal places used on the LCD.
Primary Index Level
Secondary Index Breakpoint
Values Range: 0.0 to 99999
Related P054 Breakpoints Levels (Universal Volume Calculation)
Cone Cylinder
V = (1/3)πr
2
hV = πr
2
h
Primary Index Level
Values
0 No digits after the decimal point
1 1 digit after the decimal point
2 * 2 digits after the decimal point
3 3 digits after the decimal point (limited by device resolution)