Page 126 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Parameters
P052 Tank Dimension A [MR 200]
Dimension A as used in P050 Tank Shape.
Enter one of the following:
• height of the tank bottom if P050 = 2,3,4, or 5
OR
• length of one end section of the tank if P050 = 7, in Units (P005)
P053 Tank Dimension L [MR 200]
Dimension L as used in P050 Tank Shape.
Enter the following:
• tank length (excluding both end sections) if P050 = 7
P054 Level Breakpoints (Universal Volume Calculation)
[MR 200]
When the tank shape is too complex for any of the preconfigured shapes, you can specify
the volume based on segments. See “Accessing a Secondary Index” on page 117
for
more information.
Enter the following:
• up to 32 level breakpoints (where volume is known) if P050 = 9 or 10
Entering a Level Breakpoint
1. Go to Parameter P054.
2. For each index enter a breakpoint in measurement units.
3. Ensure that each breakpoint corresponds to the same index for P055.
Primary Index Level
Values
Range: 0.0 to 99.00 m (or equivalent depending on units)
Preset: 0.000
Related • P050 Tank Shape
Primary Index Level
Values
Range: 0.0 to 99.00 m (or equivalent depending on units)
Preset: 0.000
Related • P050 Tank Shape
Primary Index Level
Secondary Index Breakpoint
Values
Range: 0.0 to 99.00 m or Max. volume (P051) (or equivalent depending on
units)
Related • P055 Volume Breakpoints