7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 121
mmmmm
Parameters
P003 Maximum Process Speed
Determines level change reaction.
Use a setting just fast enough to keep up with your process. Slower settings provide
higher accuracy. Faster settings allow for more level fluctuations.
P004 Transducer
Specifies the Siemens Milltronics transducer connected to the unit.
Primary Index Transducer
Values
1 Slow (0.1 m/min)
2 * Medium (1 m/min)
3 Fast (10 m/min)
Alters
P070 Failsafe Timer
P700 Max Fill Rate
P701 Max Empty Rate
P702 Filling Indicator
P703 Emptying Indicator
P704 Rate Filter
P710 Fuzz Filter
P713 Echo Lock Window
P727 Scan Delay
P841 Long Shot Number
Related
Failsafe (P070 to P072)
•P121 Pump by Rate
Rate (P700 to P708)
Measurement Verification (P710 to P713)
Transducer Scanning (P726 to P729)
P905 Transmit Pulse
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values
0 * No transducer attached (preset for Dual Point)
1ST-25
2ST-50
100 STH
101 XCT-8
102 * XPS-10 (preset for Single Point Model)
103 XCT-12
104 XPS-15
112 XRS-5
250 mA input [MR 200]
Related
mA Input (P250 to P260)
P842 Short Shot Frequency
P843 Long Shot Frequency
P844 Short Shot Width
P845 Long Shot Width
P852 Short Shot Range