Parameters
P003 Maximum Process Speed
Determines level change reaction.
Use a setting just fast enough to keep up with your process. Slower settings provide
higher accuracy. Faster settings allow for more level fluctuations.
P004 Transducer
Specifies the Siemens Milltronics transducer connected to the unit.
Primary Index Transducer
Values
1 Slow (0.1 m/min)
2 * Medium (1 m/min)
3 Fast (10 m/min)
Alters
• P070 Failsafe Timer
• P700 Max Fill Rate
• P701 Max Empty Rate
• P702 Filling Indicator
• P703 Emptying Indicator
• P704 Rate Filter
• P710 Fuzz Filter
• P713 Echo Lock Window
• P727 Scan Delay
• P841 Long Shot Number
Related
• Failsafe (P070 to P072)
•P121 Pump by Rate
• Rate (P700 to P708)
• Measurement Verification (P710 to P713)
• Transducer Scanning (P726 to P729)
• P905 Transmit Pulse
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values
0 * No transducer attached (preset for Dual Point)
1ST-25
2ST-50
100 STH
101 XCT-8
102 * XPS-10 (preset for Single Point Model)
103 XCT-12
104 XPS-15
112 XRS-5
250 mA input [MR 200]
Related
• mA Input (P250 to P260)
• P842 Short Shot Frequency
• P843 Long Shot Frequency
• P844 Short Shot Width
• P845 Long Shot Width
• P852 Short Shot Range