Instruction manual

7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 119
mmmmm
Parameters
P000 Lock
Secures the MultiRanger from changes via the handheld programmer.
Access this parameter directly (type 000) and enter any value (except 1954) to secure
programming lock. To unlock the MultiRanger, access this parameter and enter 1954.
Quick Start (P001 to P007)
P001 Operation
Sets the type of measurement required for the application.
Notes:
This lock only applies to the handheld programmer: it does not lock access
through communications.
A remote master can change configuration if P799 is set to allow this.
Primary Index Global
Values
1954 * OFF (programming permitted)
-1
Simulation Controls (relays energize based on simu-
lated level)
other lock activated (programming secured)
Related Simulation on page 85
WARNING:
Use this lock as backup security only. It uses a fixed value which can
be discovered by unauthorized personnel.
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values
0Out-of-service
1 Level – how full the vessel is (MR 200: volume – P050)
2 Space – how empty the vessel is (MR 200: ullage – P050)
3 * Distance – distance from transducer to material
4 DPD – dual point difference [MR 200]
5 DPA – dual point average [MR 200]
6 OCM – flow rate in an open channel [MR 200]
7 Pump Totalizer – total pumped volume [MR 200]
Alters P600 Primary Measuring Device