Instruction manual

Page 110 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Data Types
Relay Function Codes (P111 Only)
Please note that the MultiRanger 200 offers more function codes.
If a device parameter returns a relay function code, that message is converted to a
number and is then provided in the register. The numbers are shown in the following
table:
MultiRanger 100
MultiRanger 200
See P111 on page 134 of the
Parameter Reference
section.
Control Relay Function Code Number P111
General OFF, relay not used 0 0
Undesignated Level Alarm 1 1
Low-Low Level Alarm 2 1 – LL
Low Level Alarm 3 1 – L
High Level Alarm 4 1 – H
High-High Level Alarm 5 1 – HH
Loss of Echo (LOE) Alarm 20 6
Transducer Cable Fault Alarm 16 7
Pump Fixed Duty Assist 25 50
Alternate Duty Assist 30 52
Control Communication 66 65
Control Relay Function Code Number P111
General OFF, relay not used 0 0
Undesignated Level Alarm 1 1
Low-Low Level Alarm 2 1 – LL
Low Level Alarm 3 1 – L
High Level Alarm 4 1 – H
High-High Level Alarm 5 1 – HH
In Bounds Alarm 6 2
Out of Bounds Alarm 9 3
Rate of Level Change Alarm 12 4
Temperature Alarm 15 5
Loss of Echo (LOE) Alarm 20 6
Transducer Cable Fault Alarm 16 7
Pump Totalizer 22 40
Flow Sampler 23 41
Fixed Duty Assist 25 50
Fixed Duty Backup 26 51
Alternate Duty Assist 30 52
Pump
(con’t)
Alternate Duty Backup 31 53
Service Ratio Duty Assist 35 54
Service Ratio Duty Backup 36 55
First In First Out (FIFO) 40 56
Control
Flush Valve 65 64
Communication 66 65