Specifications

9
SYSTEM TROUBLE DISPLAY
When a single system trouble is detected by the system (no fire alarms, or su-
pervisory alarms):
1. The TROUBLE icon will flash, and
2. The LCD display will slowly toggle between the two displays:
Display 1, top row: "SYStrbl" followed by "EXX" where XX represents the spe-
cific error code of the associated trouble, numbers from 01 to 99. The three dig-
its to the right indicate the event number, in this example it will display "001".
Display 1, bottom row: The DATE in MM/DD/YY format, followed by the time.
Display 2: System trouble description, followed be "EXX-YYY" (where XX is the
specific 2-digit error code associated with the trouble and YYY is specific device
number associated with the trouble, where applicable).
When a trouble is detected--and there are no fire or supervisory signals--but
there are additional trouble conditions on the system such as other supervi-
sory signals or troubles:
1. The TROUBLE icon will flash.
2. The LCD display will indicate the initial supervisory signal, slowly toggling be-
tween the two displays as described at left. The symbol ">" will follow the event
number to indicate that additional troubles are present in the system.
LOW BATTERY
E02-000
SYStrbl E02 001
11/01/12 12:05 AM
Display slowly scrolls
between these 2 screens
SUPV.
SUPV.
LOW BATTERY
E02-000
SYStrbl E02 001>
Display slowly scrolls
between these 2 screens
SUPV.
SUPV.