Specifications
7
FIRE ALARM DISPLAY
ZONES FAULTED
02 BACK DOOR
BYPASSED
BYPASSED
BYPASSED
02 BACK DOOR
When a single fire alarm is detected by the system:
1. The red FIRE LED will flash, and
2. The LCD display will slowly toggle between the following two displays:
Display 1, top row: The word "FIRE" followed by the 3-digit zone #
"ZXXX" (where XXX represents numbers from 001 to 255). The three digits to
the right indicate the event number, in this example, it will display "001".
Display 1, bottom row: The date in MM/DD/YY format, followed by the time.
Display 2: Zone number followed by the zone description (entered by the
dealer).
When a fire alarm is detected and there are other conditions on the system
such as a supervisory signal, or system troubles:
1. The red FIRE LED will flash and the icons SUPV and/or TROUBLE may be
flashing or on steady.
2. The LCD display will indicate the initial fire alarm, slowly toggling between the
two displays as described at left. The symbol ">" will follow the event number
to indicate that additional events/conditions have occurred in the system.
Press NEXT to view any subsequent fire alarms and/or events of lower priority.
123-SMK NW STAIR
3RD FLOOR
FIRE Z123 001
11/01/12 12:05 AM
Display slowly scrolls
between these two screens
123-SMK NW STAIR
3RD FLOOR
FIRE Z123 001>
11/01/12 12:05 AM
Display slowly scrolls
between these 2 screens