Specifications

34
E97-NNNNNN
SYStrbl E97 xxx
MM/DD/YY HH:MM
'FslcPnt Trouble'
'E97-NNN XXXXXX'
Trouble detected on a Fire SLC device. Each device generates troubles specific to its Type (see list numbered 1-9 below) and all
troubles are indicated with this trouble except the E66 "CleanSmk" sensitivity trouble. NNN is the associated zone number; XXXXXX is
the Device Six-Character ID number (the second number from left is the "Type" as per the list below). To determine the specific trou-
ble, PCD-Windows Quickloader "Status Upload" must be performed. Each device Type is as follows:
1: FWC-FSLC-SMK Photoelectric Smoke
2: FWC-FSLC-HEAT Heat Sensor
3: FWC-FSLC-PULL Analog Manual Pull Station
4: FWC-FSLC-EZM1 (-EZM1B) Fast Response Contact Monitor Module
5: FWC-FSLC-SOM1 Supervised Output Module
6: FWC-FSLC-RM2 Dual Relay Module
7: FWC-FSLC-DUCT Photoelectric Duct Sensor
8: FWC-FSLC-EZM2 Dual Input Monitoring Module
9: FWC-FSLC-CZM Conventional Zone Module
TBL #
FIRE KEYPAD DISPLAY
KEYPAD TROUBLE DESCRIPTION
SYSTEM TROUBLE ERROR CODES