Specifications
33
TBL #
FIRE KEYPAD DISPLAY
KEYPAD TROUBLE DESCRIPTION
SYSTEM TROUBLE ERROR CODES
E72-00
SYSTrbl E72 xxx
MM/DD/YY HH:MM
'RFRec High Noise'
'E72-000 SERVICE '
Wireless Radio Receiver High Noise. Extraneous wireless signals are being detected. Try re-locating the GEMC-RECV
receiver to a quieter position. XXX is the receiver number.
E90-00
SYStrbl E90 xxx
MM/DD/YY HH:MM
'FslcRec Mem Fail'
'E90-000 SERVICE '
Fire or Burglary SLC module memory failure. Indicates the onboard memory of the SLC device is not working as intended.
Attempt to correct by downloading via PCD-Windows Quickloader download software. Replace module if trouble persists.
E91-00
SYStrbl E91 000
MM/DD/YY HH:MM
'NLM SUPV TROUBLE'
'E91-000 SERVICE '
NL-MOD supervision trouble.
A problem has been detected with the NL-MOD. Caused when control panel is not communicating with the NL-MOD; either
the NL-MOD is not working properly or it is not connected to the control panel. Check the 4 wire harness. This error is report-
able.
E92-000
SYStrbl E92 xxx
MM/DD/YY HH:MM
'FslcRec Unmapped'
'E92-000 SERVICE '
"Unmapped" Device Trouble. One or more Fire SCL device(s) associated with the GEMC-FW-SLC Fire SLC module was
found on the loop but not mapped (programmed) to any zone.
E94-000
SYStrbl E94 xxx
MM/DD/YY HH:MM
'FslcRec NoRespon'
'E94-000 SERVICE '
For Fire Systems: A response failure in the GEMC-FW-SLC Fire SLC Module.
Ensure the associated SLC Module is correctly addressed and its wiring harness is placed in the correct connector (SLC #1 or
SLC #2).
E96-000
SYStrbl E96 xxx
MM/DD/YY HH:MM
'FslcRec LoopTrbl'
'E96-000 SERVICE '
GEMC-FW-SLC Fire SLC Module wiring trouble. Short detected on Class B loop; open or short detected on a Class A loop.
Check SLC loop wiring connections. NNN = module number.