Specifications
31
SYSTEM TROUBLE ERROR CODES
E19-00
'SystemMemoryFail'
'E19-00 SERVICE'
Internal User Program memory error.
Fire Keypads: Unlock keypad and press RESET to clear.
Burg Keypads: Select menu option RESET SYSTEM TBL then press ENTER.
E20-00
SYStrbl E20 xxx
MM/DD/YY HH:MM
'Panel Memory ERR'
'E20-000 SERVICE '
Internal Program memory error.
Fire Keypads: Unlock keypad and press RESET to clear.
Burg Keypads: Select menu option RESET SYSTEM TBL then press ENTER.
E24-00
SYStrbl E24 xxx
MM/DD/YY HH:MM
'TIME FOR SERVICE'
'E24-00 SERVICE '
A service message can be programmed through the PCD-Windows Quickloader (event-schedule screen) to remind the user
to arrange for scheduled maintenance. At the programmed date and time, the keypad sounder will start to pulse and the
display will read "TIME FOR SERVICE".
Fire Keypads: Unlock keypad and press RESET to clear.
Burg Keypads: Select menu option RESET SYSTEM TBL then press ENTER.
E26-00
SYStrbl E26 xxx
MM/DD/YY HH:MM
'System Gnd Fault'
'E26-000 SERVICE '
System Ground Fault. A system wire is shorted to earth ground.
E27-00
SYStrbl E27 xxx
MM/DD/YY HH:MM
'Printer Trouble '
'E27-001 SERVICE '
Printer communication failure. Check printer connections.
E28-00
SYStrbl E28 xxx
MM/DD/YY HH:MM
'ErrorCheck Req'
'E28-000 SERVICE '
Fire System is in "ENABLE PROGRAMMING" mode ("ENABLE PROGRAMMING" is entered via the Keypad Function
menu) and therefore may not be relied upon to perform as intended. The system account program must be downloaded with
PCD-Windows performing an error check. The system must always be tested after download to confirm proper operation.
Access to panel programming must be enabled via the above described keypad Function menu to allow keypad programming
or remote downloading of FIRE-related programming changes.
TBL #
FIRE KEYPAD DISPLAY
KEYPAD TROUBLE DESCRIPTION