Specifications

29
SYSTEM TROUBLE ERROR CODES
TBL #
FIRE KEYPAD DISPLAY
KEYPAD TROUBLE DESCRIPTION
E03-00
SYStrbl E03 xxx
MM/DD/YY HH:MM
' Comm Failure '
'E03-000 SERVICE '
Communication Failure: The system was not able to report to the central station. If this is due to a temporary interruption in
the telephone service, the trouble can be cleared when the service is restored by performing a Communication Test:
Fire Keypads
1. Enter code to unlock keypad and press MENU.
2. Press MENU until "ACTIVATE DIALER TEST" appears in the window.
3. Press ENTER to send a test signal to the central station.
4. Allow a minute or 2 for the call to reach the central station then press RESET.
Burg Keypads:
1. While disarmed, enter your User Code followed by MENU.
2. Answer NO until "ACTIVATE DIALER TEST" appears in the window.
3. Press YES to send a test signal to the central station.
Note: Will also display if panel improperly programmed to report (Report Alarm, Report Codes, Subscriber ID Numbers, etc.
must be programmed correctly).
E04-NNNNNN
SYStrbl E04 xxx
MM/DD/YY HH:MM
'RFPnt Supv Trbl'
'E04-NNN XXXXXX'
Wireless Transmitter or SLC Point Supervison Failure. A problem has been detected either in a wireless transmitter or a
burglary SLC Point. "XXXXXX" = The wireless/SLC device 6-digit ID map number. NNN = associated zone number
E05-NN
SYStrbl E05 xxx
MM/DD/YY HH:MM
'RFPnt LowBattery'
'E05-NNN XXXXXX'
Wireless Transmitter Low Battery. The battery in a wireless transmitter is low and should be replaced. This transmitter is
on the zone corresponding to the number NN. Warning: Replace batteries only with the same type as specified on the
sticker mounted on the device or in the installation instructions. Use of another battery may present a risk of fire or explosion.
Do not recharge or disassemble battery, or dispose of in fire. "XXXXXX" = The wireless device 6-digit ID map number. NN or
NNN = Zone number.
E06-NN
SYStrbl E06 xxx
MM/DD/YY HH:MM
'RFRec NoResponse'
'E06-000 SERVICE '
RF Receiver or SLC Module response trouble. NN = Receiver or SLC Module address (1-4). Check connection to re-
ceiver/SLC module, check Receiver wiring is on correct bus Fire or Burg and/or correct SLC connector SLC1 or SLC2, check
to make sure address jumper on receiver or SLC Module is correct. Make sure no duplicate addresses are used.
For Burglary keypads, NNN = receiver number (1-4).