Fire Watch
A fire watch is implemented to en-
sure the fire-safety of a building or
an area in the event of any act
(such as entering One Man Test
mode) that creates an increased
risk to persons or property.
The term "Fire Watch" is used to
describe a dedicated person or
persons whose sole responsibility
is to look for fires within an estab-
lished area.
Enter One Man Test mode as follows:
1 Enter the Function Menu by first unlocking the keypad (see Unlocking the
Keypad on page 10) then press MENU.
2 Skip through the function by pressing MENU until "DO ONE MAN TEST" ap-
pears in the keypad display.
3 Press ENTER or NEXT to enter the mode. The words "ONE MAN TEST
MODE, SYSTEM OFF LINE" appears in the keypad display.
During One Man Test mode, all zones are disabled from activating bell outputs,
door release circuits and from reporting alarms to the central monitoring station.
Therefore, the Fire Warden must be notified and must initiate a Fire Watch dur-
ing this time (see sidebar at left). A signal is sent to the central station to notify
the monitoring station that the system is under a test. To exit One Man Test
mode, press RESET on any keypad to automatically re-enable all zones and
send a signal to the central station that the system has returned to normal op-
eration.
While in One Man Test mode, as smoke sensors and other devices are trig-
gered, the bell output will sound a "ding" once; when the sensor or circuit is re-
stored, the bell output will "ding" twice.