Specifications

11
SILENCING AND RESETTING A FIRE ALARM
ZONES FAULTED
02 BACK DOOR
BYPASSED
BYPASSED
BYPASSED
02 BACK DOOR
When a fire alarm is detected by the system, the keypad must be "unlocked" to
view the total system status, silence audible alarms and reset the system (see
Unlocking the Keypad on page 10).
Press the ACK. button to acknowledge the fire alarm and silence the local keypad
sounder. The Fire alarm LED will change from flashing to steady.
The "KEYPAD UNLOCKED" message will display for several seconds.
Press NEXT to view the next condition if ">" displays after the event number (the
event numbers start with number "001" as shown in the example at left).
Continue to view all events. When the event number returns to "001", all events
have been viewed. To review the status of events, the PRIOR and NEXT buttons
may be used to scroll back and forward through the events.
123-SMK NW STAIR
3RD FLOOR
FIRE Z123 001>
11/01/12 12:05 AM
KEYPAD UNLOCKED
123-SMK NW STAIR
3RD FLOOR
FIRE Z123 001>
11/01/12 12:05 AM
129-PULL STATION
2ND FLOOR
FIRE Z129 002>
11/01/12 12:05 AM