Operating instructions
SHERWOOD LPG PRODUCTS
Instruction Sheets
Operating Instructions for Sherwood 2341 Series Transfer Valve —
Instruction Sheet I-2341
tLeaking gas can cause fires or explosions
tOnly trained personnel should work on gas systems
tInspect gas systems regularly
tReplace equipment as required
READ THIS INSTRUCTION COMPLETELY BEFORE BEGINNING.
General
This instruction is intended for people familiar with LP gas equipment and
applications. IF YOU ARE NOT FAMILIAR WITH THIS EQUIPMENT — STOP.
This instruction covers the use of the Sherwood 2341 Series Transfer Valve
and PA5138 Adapter to withdraw liquid LP gas from stationary or domestic
tanks that have been pre-fitted with a Sherwood PVE5136 or PVE5137
Checkmate
™
as shown in Figure 1.
ALL THREE COMPONENTS ARE NECESSARY TO REMOVE LIQUID LP GAS.
At low temperatures, (less than 15º F), the excess flow valve in the
Checkmate
™
may not close due to inadequate vapor pressure in the tank.
Refer to NPGA Bulletin #113-90 for more information.
These components are designed to evacuate liquid LP gas from a stationary
tank in case of an emergency or if the tank must be relocated.
The transfer valve and adapter must not be used as a permanent outlet
and MUST BE REMOVED FROM THE CHECKMATE WHEN THE LIQUID
TRANSFER IS COMPLETE.
All Safe, Inc. 1-866-958-3473