9.2.2 Monitoring Function (of Firmware REV03 or Later)
After connecting the cable, power on the module. The following message will be
displayed.
-------------------------------------
Press Enter for configuration menu
-------------------------------------
NOTE: I/O exchange will be halted
-------------------------------------
Press <Enter>. The main menu is displayed.
-------------------------------------
AnyBus M AS-i Main Menu
-------------------------------------
1 - View scan-lists
2 - View all nodes
3 - View all detected nodes
4 - View single node
5 - Toggle Protected/Configuration
6 - Toggle online/offline
7 - Toggle auto addressing On/Off
8 - Save configuration
-------------------------------------
Offline phase active: False Power fail: False
Normal operation: True Slave 0 exists: False
Configuration match: True Periphery fault: False
Address collision: False EEPROM status: OK
Auto address enable: On Auto address assign: False
Offline mode: Online
Autoprogramming: Not possible
Operation mode: Configuration
>
CAUTION
When the monitor enters connected state, input relay X32 turns on, and
input/output update from user programs is suspended.
When the monitor is disconnected, normal operation resumes. For information on how to
disconnect, read the documentation of the terminal emulator software.
CAUTION
Periphery fault as reported by the monitoring function differs from the operation of the
PERIPHERAL_FAULT(V2.1) input relay (X29). The monitoring function also
displays “Periphery fault” as True when in offline state or when ASi power failure is
detected.
CAUTION
Ignore the “Address collision” and “Auto address assign” values reported by the
monitoring function.