HOW TO CHANGE THE SETPOINT
1. Push the SET key for more than 2 seconds to change the Set point value;
2. The value of the set point will be displayed and the LED under COMP starts blinking;
3. To change the Set value push the UP or DOWN arrows within 10s.
To memorize the new set point value push the SET key again or wait 10s.
HOW TO CHANGE a parameter value
1. Enter the Programming mode by pressing the SET and DOWN keys for 3 seconds
(LEDs under DEF and COMP start blinking).
2. Select the required parameter by pushing
the UP or DOWN arrows
3. Press the “SET key to display its value (now only the COMP LED is blinking)
4. Use UP” or “DOWN” to change its value
5. To exit: Press SET + UP or wait 15s without pressing a key.
NOTE 1: The set value is stored even when the procedure is exited by waiting the time-out to expire.
NOTE 2: Master-Bilt’s SETPOINT is set at a recommended –10°F at the factory for low temperature(LT) and
+35
o
F for medium temperature(MT) application.
NOTE 3: To scroll down the parameters without changing them, press the DOWN button.
LIST OF PARAMETERS
Here is a list of the parameters the value of which can be changed in the programming mode, as
well as their ranges.
Master-Bilt’s
Setting
Parameter Display
Symbol
Description Range
BLG
Temperature Set
Point
Set
When this temperature is
reached the compressor LED
will be off
-16 to 5°F
-10°F or -15°F
Temperature
Differential
Hy
Cut-out temperature is Set + Hy
1 to 255°F
10
Maximum
Temperature
Alarm
ALU
230°F
15
Minimum
Temperature
Alarm
ALL
-58°F
-25
Temperature
Alarm Delay
Ald
0 to 255 min
30
Room Probe
display
dP1
Evaporator
Probe Display
dP2