Service manual

Residential Packaged Units - 60Hz Puron
®
20
Electrical - Line Voltage
WARNING! CAUTION!
WARNING! To avoid possible injury or death due to
electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.
CAUTION! Use only copper conductors for eld installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Table 4a: GT-PX (50YD) Series Electrical Data
Table 4b: GT-PG (50YE) Series Electrical Data
Rated Voltage of 208-230/60/1 Min/Max Voltage of 197/254
HACR circuit breaker in USA only All fuses Class RK-5
All TT Units with Emerson ECM Fan Motor TT Units (ECM) Standard TT Units (ECM) with ClimaDry
Model
Compressor
HWG
Pump
FLA
Ext
Loop
Pump
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
(2)
ClimaDry
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max/
Fuse
HACR
(2)
RLA LRA Qty
026 11.7 58.3 1 0.5 4.0 3.9 20.1 23.0 30 0.8 20.9 23.8 35
038 15.3 83.0 1 0.5 4.0 3.9 23.7 27.5 40 0.8 24.5 28.3 40
049 21.2 104.0 1 0.5 4.0 6.9 32.6 37.9 50 1.1 33.7 39.0 60
064 27.1 152.9 1 0.5 4.0 6.9 38.5 45.2 70 1.1 39.6 46.3 70
072 29.7 179.2 1 0.5 4.0 6.9 41.1 48.5 70 1.1 42.2 49.6 70
Rated Voltage of 208-230/60/1 Min/Max Voltage of 197/254
HACR circuit breaker in USA only All fuses Class RK-5
All 50YD Units
50YD Units
50YD Units (ECM) with Whole House
Dehumidi cation
Whole
House
Dehumid.
Pump FLA
Standard TS Unit TS Unit with ClimaDry
Model
Compressor
HWG
Pump
FLA
Ext
Loop
Pump
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
(2)
ClimaDry
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max Fuse/
HACR (2)
RLA LRA Qty
PSC Electrical Data
018 9.0 48.0 1 0.40 4.0 1.0 14.4 16.7 25 0.8 15.2 17.5 25
024 13.5 58.3 1 0.50 4.0 1.6 19.6 22.9 35 0.8 20.4 23.7 35
030 12.8 64.0 1 0.50 4.0 1.8 19.1 22.3 35 0.8 19.9 23.1 35
036 16.0 77.0 1 0.50 4.0 1.8 22.3 26.3 40 0.8 23.1 27.1 40
042 16.7 79.0 1 0.50 4.0 2.2 23.4 27.5 40 0.8 24.2 28.3 45
048 21.8 117.0 1 0.50 4.0 2.7 29.0 34.4 50 1.1 30.1 35.5 50
060 26.4 134.0 1 0.50 4.0 3.8 34.7 41.3 60 1.1 35.8 42.4 60
ECM Electrical Data
018 9.0 48.0 1 0.40 4.0 3.9 17.3 19.6 25 0.8 18.1 20.4 25
024 13.5 58.3 1 0.50 4.0 3.9 21.9 25.2 35 0.8 22.7 26.0 35
030 12.8 64.0 1 0.50 4.0 3.9 21.2 24.4 35 0.8 22.0 25.2 35
036 16.0 77.0 1 0.50 4.0 3.9 24.4 28.4 40 0.8 25.2 29.2 45
042 16.7 79.0 1 0.50 4.0 3.9 25.1 29.2 45 0.8 25.9 30.0 45
048 21.8 117.0 1 0.50 4.0 6.9 33.2 38.6 60 1.1 34.3 39.7 60
060 26.4 134.0 1 0.50 4.0 6.9 37.8 44.4 70 1.1 38.9 45.5 70
070 30.8 178.0 1 0.50 4.0 6.9 42.2 49.9 80 1.1 43.3 51.0 80