Owners Guide

13
shows a temperature warmer than the adjusted seng, the thermostats contacts close, compleng
the circuit that operates the compressor. The compressor takes in the low pressure refrigerant gas and
converts it to high pressure refrigerant gas. Passing through the condenser (radiator), the refrigerant
gas gives o heat to the air surrounding the condenser, by way of the cooling ns, like any radiator. Dur-
ing this process the high pressure refrigerant gas changes state as it loses heat, coming out of the
condenser as a high pressure liquid refrigerant. The dryer / lter blocks parcles, and contains a des-
sicant to remove moisture from the refrigeraon system. Moisture (water) in the refrigeraon system
can damage or cause the refrigeraon system to fail. This is due to the moisture reacng with the re-
frigerant gas to form corrosive acids and sludge that can aack internal refrigeraon components caus-
ing them to fail and / or clogging the capillary tube that stops the refrigeraon system from cooling the
refrigerator and freezer. These acids and sludge that are formed by their reacon with moisture are
powerful, toxic substances. Refrigeraon manufacturers go to great lengths to remove as much mois-
ture and air from the refrigeraon system before they inject the refrigerant gas into the system and seal
it.
b. From the output side of the dryer/lter, the high pressure liquid ows through the evaporator, which
in fact is incorporated into the oor and ceiling of the freezer compartment of the refrigerator. In this
process, the refrigerant lowers temperatures by absorbing heat from the interior of the refrigerator,
changing in the process to low pressure liquid refrigerant, then to a low pressure refrigerant gas.
c. On g. 2-2, look at the starter relay. This relay performs 2 important funcons: It brings both the
thermostat and condenser fan motor into the compressor start circuit, and it provides the required
sequence for bringing the compressor to full power. When the thermostat closes, the circuit between
the 115 volt power cord and the terminal of the starter relay is completed, and electricity ows
through the starter relay and into the start-up and run windings of the compressor. The compressors
electrical motor comes up to speed within one or two seconds and in doing so, allows the power to the
starter windings to be disconnected by way of its relay. Also the compleon of the electrical circuit pro-
vides power to the condenser fan motor. If the fan does not operate the compressor will overheat and
cycle o by way of its thermal overload. Connecons are shown in g. 2-2. Noce that EITHER fan mo-
tor line can be connected to either terminal on the compressor starter relay. Looking at the connecons
you will see that each of the two fan motor lines go to each terminal, secured by a spade lug connec-
on.
d. The element marked accumulator is a secon of the evaporator that acts as a reservoir, keeping the
return line to the compressor lled with low pressure refrigerant gas.
e. The refrigeraon system cannot funcon without proper operaon of the fan.
f. Fig. 2-2 shows a system that uses a 230 VAC power source. If your system uses a primary source of
115 VAC, the transformer is not required: plug the 115 VAC electrical plug into the 115 VAC outlet.
g. Noce that the 115 VAC power cord’s green wire and a short green wire from one to the compres-
sors mounng brackets are secured by screws to the cabinets bare metal base plate. See also g. 3-1,
No. 5.
h. Refer to g. 2-2. It is important to noce that a failure of the starter relay can appear to be a failure
of the compressor. When the relay funcons as it should in normal operaon, closing of the thermo-
stats relay allows 115 VAC to ow from the black lead of the refrigerators power cord through the con-
tacts of the thermostat, along the return wire lead from the thermostat to the compressors overload,
then to the starter relay. The relay acvates the compressor and condenser fan motor. The white lead