Specifications

THE SHALLECK COLLABORATIVE SANTA ROSA CITY COUNCIL
AV SYSTEMS UPGRADE
April 6, 2012 27 41 16  18 AV SYSTEMS
100% CD
C. As much as possible, maintain separation of signal types when outside of conduit.
D. No cable shall be installed with a bend radius less than recommended by the manufacturer.
E. Cables types shall be as indicated on the Drawings. In plenum spaces, provide the plenum
version of the specified cable type.
3.03 PROTECTION OF PROPERTY:
A. Contractor is responsible to provide protection for all equipment, tools and materials delivered
to the Project Site prior to final acceptance by Owner. Any loss or damage is the
responsibility of the contractor, until final acceptance by Owner.
3.04 SEQUENCING:
A. The contractor shall not install any electronic equipment until the room where the equipment
shall be located has been finally painted or otherwise finished, and cleaned by the Contractor
or Owner’s Representative. Any damage to equipment resulting from failure to follow this
requirement will result in the contractor replacing the damaged equipment at their cost.
3.05 COMMISSIONING AND DEMONSTRATION:
A. Coordinate with Division 26.
B. Appropriately trained personnel shall review, test, program and otherwise complete the
system, following completion of installation.
C. Upon completion of the installation, the Contractor shall notify the Owner’s Representative
that the system is available for formal checkout. Notification shall be provided in writing.
Checkouts shall be scheduled in accordance with the Owner’s Representative’s schedule.
D. Provide to the Owner’s Representative and or his Consultant the following upon arrival:
1. Measurements showing all Ethernet wiring complies with Category 5e or Category 6
requirements for full bandwidth operation.
2. Verification that every line has been sweep tested and conforms to standard
requirements per signal level.
3. Demonstration of input and output of signal throughout the entire system.
E. Make available for review by the Owner’s Representative and or his Consultant:
1. All components for physical inspection and inventory.
2. A computer to access any DSP units.
3. All installed devices in full operation, with no temporary equipment in place.
4. All portable devices, fully complete, and available to test at all plugin locations.
5. Test equipment, including:
a. High quality media for every presentation source
b. Analog & Digital video test generators
c. Portable TV with CATV receiver input
d. AC voltmeter
e. Sound level meter
f. Portable amplified loudspeaker
g. Waveform monitor (oscilloscope)
h. Audio analysis equipment (provides real time display, pink noise source, test
oscillator, level and THD+N measurements)
i. Cablesets, adapters, and connectors for inserting the test equipment into and out of
the system’s user interfaces and connector plates.