B) AIR RECEIVERS
1 no. of Air Receiver of 4 m3 capacity for instrument air and
2 no. Air Receivers of capacity 6 m3 for plant air at 8 kgf/cm2(g)
operating pressure, complete with all fittings such as safety valves, drain
connection with auto condensate trap and bypass valve, vent
connections and all inlet and outlet connections with companion flanges,
supporting arrangement, access platforms, instruments etc. The
material of construction will be as per IS 2002 Gr. 2A . The air
receiver will be designed, manufactured and tested according to IS
7938, 1976 (RA 1991).
C) COOLING TOWER
Quantity : Three (3) sets (2W+1S) each of 40 cum/hr.
Type : Induced draft counter flow
Casing/ Basin : FRP
Frame Work : MS hot dip galvanized
Fills : PVC
Nozzles : Brass
Bolts, nuts, miscellaneous hardware : MS electro galvanized
Fan hub & blades : Cast Aluminium
Fan type : Axial flow, direct drive
Fan speed : 720 rpm
Degree of protection of motor : IP 55 (temperature rise limited to class
Ladder : Galvanised steel ladder with safety cage & hand railing up to
the top of tower. Inclined to 30
0
to the vertical
Eliminators : No. of deflector to be arranged to reduce drift loss < 0.2%
of water circulation.
Cooling Tower Accessories:
(i) Level switch at cooling tower basin (to be interlocked with pump)
(ii) Make up connection with float valve (float made of copper) &
back up ball valve
(iii) Quick fill connection with ball valve
(iv) Overflow connection
(v) Drain connection with ball valve
(vi) GI wire mesh 18 gauge strainer
(vii) Equalizing line of cooling towers with isolation valves