Install Instructions
4 
MAINTENANCE
Routine maintenance is required to keep this product 
operating at its peak performance and efficiency. Over 
time, the housing, air intake grille, air intake filter, 
blower wheels and motor(s) will accumulate a build up 
of dust, debris and other residue. It is imperative to 
keep these components clean. Failure to do so will not 
only lower operational efficiency and performance, but 
also reduce the useful life of the product. The time 
between cleanings depends on the application, location 
and daily hours of use. On average, under normal use 
conditions, the product should require a thorough 
cleaning once every six (6) months. 
To clean the product, perform the following: 
1.  Verify the product has been disconnected from the 
power source. 
2.  Use a damp cloth and either a warm mild soapy water 
solution or bio-degradable degreaser, to wipe down 
the exterior components of the housing. 
3.  To access the interior of the product, remove the air 
intake grille and/or air intake filter. This is 
accomplished by removing the eight (8) self-tapping 
screws on the face of each air intake grille/filter. 
4.  Thoroughly clean the air intake grille/filter. 
5.  Remove the motor fan assembly (MFA) from inside the 
air curtain housing. This is accomplished by loosening 
the watertight fitting and pulling the cord out (3 phase 
power) or by the quick disconnect plug on the motor (1 
phase power). Then remove the two (2) wing nuts on 
the out board sides of the MFA pan. Care should be 
taken to avoid the MFA from tipping over. 
6.  Remove the MFA from the unit and thoroughly wipe 
down the motor, blower wheels and blower wheel 
housings. Be careful not to submerge the motor in 
water or spray it with a water hose. 
7.  The motor(s) require no additional lubrication. They 
are permanently lubricated and feature double sealed 
ball bearings. 
8.  To re-install the product, reverse the procedures 
above. 
9.  Reconnect the power source to the product 
10. If you have any questions regarding the maintenance 
of the product, contact the manufacturer. 
SPECIAL APPLICATIONS 
Outdoor Installation 
For outdoor unit special consideration may be required 
for enclosure, motor, wheel and other components to 
minimize damage caused by exposure to the outdoor 
elements. Contact factory for special construction and 
costing. 
Freezer and Cooler Installation 
Air curtain must be mounted on the warm side for 
optimal performance. Variable Frequency Drive (VFD) is 
strongly recommended to control the air curtain air flow 
velocity at the floor level. 
High humid areas may require de-humidifier or 
additional defrost cycle to minimize condensation and 
freezing for freezer applications. We recommend the air 
curtain unit to not replace doors but work in conjunction 
with door opening sequence cycle. 
Contact factory for details. 
a control panel or an On/Off switch, open the door 
to energize the product. 
J.  If heated products are installed, reference Heated 
Products Supplement. 
K.  For three phase units, verify direction of rotation of 
blower wheels (note direction arrows on the blower 
wheel housing). Correct if needed by changing 
polarity of three phase power. 
L.  VERY IMPORTANT Using a clamp meter, measure 
the amperage to each motor and ensure that they 
do not exceed the amperage listed on the product 
label. 
M.  If applicable, adjust the air intake grille(s) such that 
the output air stream reaches the floor. For 
temperature control and environmental separation 
applications, the air stream should reach the floor 
with sufficient strength to create an air seal around 
the door opening without creating turbulent mixing 
of the inside and outside air. For flying insect 
control applications, the air stream should reach the 
floor with maximum strength. If after proper 
installation and adjustment, the product appears to 
be producing too little or too much air for the 
application, contact the manufacturer. 
 WARNING 
Prevent hazard of electrical shock. More than one 
disconnect switch may be required to de-energize this 
product. 
 WARNING 
To reduce the risk of fire, electrical shock or injury to 
persons, observe the following: 
A. Maintenance is to be performed only by qualified 
personnel who are familiar with local codes and 
regulations and are experienced with this type of 
product. 
B. Before servicing or cleaning the product switch power 
off at service panel and lock service panel to prevent 
power from being switched “ON” accidentally.