Owner`s manual
1. Press TEMP+, then JETS 1, then SPA LIGHT.
2. Press TEMP+ repeatedly until “gFC” is displayed, then press JETS 1.
3. Press TEMP+ until “gC.n” is displayed, then press JETS 1 to clear the GFCI
Status; you will see gS.A” displayed verifying that the GFCI Status has been
set to “Armed”. System will exit in 30 seconds if no buttons are pressed.
*When you enter the GFCI menu, it always shows you the current status first.
“gS.P” means that it’s Passed (and will do no further automated GFCI Trip
Tests), “gS.A” means that it’s Armed (and will do an automated GFCI Trip Test
in 24 hours, unless a manual GFCI Trip Test is done before that). (“gS.t”, which
you are unlikely to see unless you’ve just initiated a Trip manually, means that
it’s about to Trip within the next dozen seconds or so.) GFCIs are available
from your authorized dealer.
120 Volt
120 Volt spas shall be plugged into a properly grounded, grounding type 15
amp receptacle on a dedicated circuit. A dedicated circuit is a circuit with no
other components that consume power, such as lights, televisions, radios,
computers, or other electronic devices. These could cause your spa to
malfunction by any of the following: unusual text on the control panel, slow
heating, poor jet action, tripping house breaker, or blown fuses. Failure to follow
these instructions could lead to premature failure of spa components that
would not be covered under the warranty. The dedicated circuit shall meet the
following specifications:
• Rated 120V, 60Hz, 15A (2 wires plus ground)
• Circuit breaker or fuse size: 15A
• The receptacle must be at least 5 feet (1.52 m) from the spa.
• The 15 foot GFCI power cord provided with the spa must be plugged directly
into the receptacle. Do NOT use an extension cord or any other adaptor.
Actual exposed length of cord will vary by model, but will never be less than
12 feet.
Convert 120 Volt to 240 Volt
120 Volt spas may be converted to operate on 240V, 50A. All connections
must be made by a licensed electrician.
1. Disconnect the power by unplugging the power cord from the receptacle,
removing the cord from the terminal block on the circuit board, and storing it
with your owner’s manual.
2. Locate the white wire connecting J11 to J32 on the circuit board. Remove
the wire and discard.
3. For 50A operation, move dip switch 10 to the OFF position.
4. Install 240V power as indicated in the 240 Volt section.
5. Rated 240V, 60Hz, 50A, three wires (#6 copper) plus ground (#8 copper),
[4 wires total].
Improperly wired spas are beyond Marquis Corp. control and are not covered
under the warranty. Other items beyond Marquis Corp. control include, but are
not limited to, damage resulting from: improper connections; accidents; failure
to follow procedures and instructions defined in the Marquis Spas
®
printed
instructions; cleaning agents; and natural occurrences including but not limited
to rodent or insect infestation, mold, lightning and other acts of nature.
INSTALLATION INSTRUCTIONS