Specifications

4. Select Enabled or Disabled.
10.9.3: Two-Way Audio
For Burglary, Fire and Medical event groups, there is an additional option that enables
Two-Way Audio for that event group – see 5.2.2: TWA Alarm Reporting.
To enable/disable Two-Way Audio for an event group:
1. From the Programming menu, select Communications, Event Options
[955].
2. Select an Event Group (Burglary, Fire or Medical).
3. Select TWA [#3].
4. Select Enabled or Disabled.
10.10: Vocal Message Dialler Event Options
Events reported using the Vocal Message Dialler are divided into event groups that
correspond with the pre-recorded event messages. This allows you to enable or disable
the Vocal Message feature for a specific group of events. For further information on this
feature, see 10.3: Vocal Message .
The vocal message event groups and their associated system events are as follows:
x Burglary [#1]
o Alarm from Zone (excluding Gas, Flood and
Environmental zones)
o Zone Tamper
o Tamper
o Duress
x Fire [#2]
o Zone Fire Alarm
o User Activated Fire Alarm
x Panic [#3]
o Zone Panic Alarm
o User Activated Panic Alarm
x Medical [#4]
o Zone Medical Alarm
o User Activated Medical Alarm
o No Motion
x System Trouble [#5]
o Battery Low
o Transmitter Low Battery
o AC Loss
o Media Loss
o Device Trouble
o Communication Trouble
o Transmitter Out of Synch.
o Control Panel Transmitter Out of Synch.
o Supervision Loss
o Zone Trouble
o FM Jamming
-78- © MARMITEK