The fluid cooler must be located at such distance and direction to
avoid the possibility of contaminated fluid cooler discharge air being
drawnintobuildingfreshairintakeducts.Thepurchasershouldob-
tain the services of a Licensed Professional Engineer or Registered
Architect to certify that the location of the fluid cooler is in compli-
ance with applicable air pollution, fire and clean air codes.
Fluid Cooler Shipment
Unless otherwise specified, the MH Fluid Cooler ships by truck (on flat bed
trailers), which lets you receive, hoist, and install the tower in one continuous
operation. Single-cell single-flow fluid coolers ship on one truck. Double-flow
and multicell fluid coolers, depending on their size, may require more than
one truck.
Responsibility for the condition of the fluid cooler upon its arrival belongs to
the trucker—as does the coordination of multiple shipments, if required.
Receiving Fluid Cooler
Prior to unloading the fluid cooler from the delivering carrier, inspect the ship-
ment for evidence of damage in transit. If damage is apparent, note the freight
bill accordingly. This will support your future recovery claim.
Find and remove the installation instruction drawings and bills of material
located in a plastic bag in the water collection basin. This information should
be kept for future reference and maintenance purposes.
Hoisting Fluid Cooler
All MH Fluid Cooler models must use hoist clips and overhead lifting for
handling assembled fluid cooler. Forklifting from base of fluid cooler is
not permitted. The clips for the top modules are located at the fan deck
level. The clips for the lower modules are located at the bottom of the mod-
ules at the water collection basin. A Hoisting-Installation label which has
hoisting dimensional information is located on the side casing near the tower
centerline. Remove tower from the carrier and hoist into place according to
the instructions on the label.
MH Fluid Cooler upper and lower modules must be hoisted and set
separately. Do not preassemble modules prior to hoisting.
Installation
Warning
Caution