Semi-Annually: If equipped, check the belt tension and condition.
If equipped with dampers, lubricate jack shaft bearings and tiebar linkage with 
silicone lubricant. If dampers are equipped with pneumatic or electric actua-
tors, the manufacturer's recommended maintenance procedures should be 
observed. If dampers are exposed to heavy dust-laden air, occasional flushing 
of the bearings with water is recommended. 
Clean and disinfect cooling tower with biocides. Systems with biofouling, high 
general bacterial counts, or positive cultures of legionella may require additional 
cleaning. Refer to “Fluid Cooler Cleaning” section—page 21. Consult your 
water treatment expert as to prudent biological evaluation testing.
Geareducer  models  used  on  MH  Fluid  Coolers  are  designed  for 
5-year oil change intervals. To maintain five-year change intervals, 
use only oil designed specifically for  these Geareducers. If, after 
five years, turbine-type mineral oil is used, the oil must be changed 
semiannually. Refer to the Geareducer User Manual for oil recom-
mendations and further instructions.
Annually: Relubricate motor(s) according to the manufacturer’s instructions. 
See instructions on the next page for towers with the motor located outside 
the plenum option.
Check to see  that all  bolts are  tight in  the fan and  mechanical  equipment 
region, including the fan cylinder and fan guard. Refer to Component User 
Manuals for torque values. 
Inspect the fluid cooler thoroughly, making maximum use of instructions given 
in the separate user manuals. Check structural bolted connections and tighten 
as required. Make preventive maintenance repairs as necessary.
Check to see  that all  bolts are  tight in  the fan and  mechanical  equipment 
region, including the fan cylinder and fan guard. Refer to Component User 
Manuals for torque values.
Every 5 Years: If equipped, change Geareducer oil. Refer to the Geareducer 
User Manual for instructions.