User manual
29
Fluid Cooler Maintenance
Some maintenance procedures may require maintenance personnel to enter
the fluid cooler. Each cased face of the fluid cooler has a door for access to
the interior of the tower.
The optional fan deck ladder—models MHF706 and MHF707—is designed and
intended solely for personnel to gain access to the fan deck. The fan deck lad-
der should not be used to enter or exit the access doors located on the cased
face of the tower unless the optional access door platform is provided.
The purchaser or owner is responsible for providing a safe method
forenteringorexitingtheaccessdoor.Useofthefandeckladder
toenterorexittheaccessdoorsmayresultinafall.
Included with this instruction packet are separate User Manuals on each major
operating component of the tower, and it is recommended that you read them
thoroughly. Where discrepancies may exist, the separate User Manuals will
take precedence.
The following is recommended as a minimum routine of scheduled mainte-
nance:
Always shut off electrical power to the tower fan motor prior to
performing any inspections that may involve physical contact with
themechanicalorelectricalequipmentinoronthetower.Lockout
and tag out any electrical switches to prevent others from turning
thepowerbackon.Servicepersonnelmustwearproperpersonal
protectiveclothingandequipment.
Weekly: Inspect for bacterial growth and general operation conditions. Bacte-
rial growth should be reported to your water treatment expert for immediate
attention.
If equipped, the damper actuator and assembly should be cycled open and
closed several times. Observe the cycle to assure that the blades and link-
age move freely. Seasonal periods where the damper assembly remains open
or closed for months at a time can allow pivot points to scale up, causing
premature failure.
Maintenance
Warning
Warning
➠